A commercial shop has the following loads : Room sensible heat = 58.15 kW Room latent heat = 14.54 kW

Image
 A commercial shop has the following loads : Room sensible heat = 58.15 kW Room latent heat = 14.54 kW The summer outside and inside design conditions are: Outside = 40°C DBT, 27°C WBT Inside = 25°C DBT, 50% RH 70 m3/min of ventilation air is used. Determine the following if thby-passe by- pass factor of the cooling coil is 0.15. (i) Ventilation load (ii) Grand total heat (iii) Grand sensible heat factor (iv) Effective room sensible heat factor (v) Apparatus dew point